Use of de-icing salt: the concrete surfaces being directly affected and the exposure classes

Eurocode 2 part 2: Design of concrete bridge structures   4.2 (106)

Where de-icing salt is used, exposed concrete surfaces within x (m) of the carriageway horizontally or within y (m) above the carriageway should be considered as being directly affected by de-icing salts. Top surfaces of supports under expansion joints should also be considered as being directly affected by de-icing salts.

Recommendation

The recommended value for x is 6 (m) and the recommended value for y is 6 (m).

The recommended classes for surfaces directly affected by de-icing salts are XD3 and XF2 or XF4, as appropriate, with covers given in Table 4.4N and Table 4.5N for XD classes.

National choice

the distance
The distance
The exposure classes
x
y
 
...
[m]
[m]
 
...